| Copper Conductor Control Cables (Unarmoured) |
TABLE-1 PVC insulated and PVC sheathed unarmoured multicore 650/1100 V grade copper conductor control cables (1.5 sq. mm & 2.5 sq. mm) |
| No. of Cores & Cross sectional area |
Conductor (Cu) Min. No. of wire |
Thickness of PVC Insulation (Nom) |
Thickness of Common covering (min) |
Thickness of PVC outer sheath (Nom) |
Approx OD |
Approx. net wt. of cable |
Normal Delivery |
Approx gross wt. |
Max. D.C. resis- tance at 20oC |
Approx AC resis- tance at operating temp. 70oC |
Approx reac- tance at 50 Hz |
Approx Capaci- tance for two adjacent cores |
Current Rating |
| Extruded |
Wrapped |
Direct in ground |
In air |
| No. x mm2 |
No. |
mm. |
mm. |
mm. |
mm. |
mm. |
Kg/Km |
|
ohm/km |
Kg/Km |
ohm/km |
ohm/km |
uf/km |
Amps. |
Amps. |
| 2 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
11.5 |
163 |
500/1000 |
208 |
12.2 |
14.5 |
0.214 |
0.1 |
23 |
20 |
| 3 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
12.0 |
185 |
do |
230 |
12.2 |
14.5 |
0.214 |
0.1 |
21 |
17 |
| 4 X 1.5 C |
- |
0.8 |
0.3 |
- |
1.8 |
13.0 |
218 |
do |
293 |
12.2 |
14.5 |
0.214 |
0.1 |
21 |
17 |
| |
| 5 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
13.5 |
253 |
do |
328 |
12.2 |
14.5 |
0.214 |
0.1 |
16 |
14 |
| 6 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
14.5 |
292 |
do |
367 |
12.2 |
14.5 |
0.214 |
0.1 |
15 |
13 |
| 7 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
14.5 |
305 |
do |
380 |
12.2 |
14.5 |
0.214 |
0.1 |
14 |
13 |
| |
| 10 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
18.0 |
420 |
500 |
560 |
12.2 |
14.5 |
0.214 |
0.1 |
13 |
11 |
| 12 X 1.5 C |
1 |
0.8 |
0.3 |
- |
1.8 |
18.5 |
461 |
do |
601 |
12.2 |
14.5 |
0.214 |
0.1 |
12 |
10 |
| 14 X 1.5 C |
1 |
0.8 |
- |
0.3 |
1.8 |
18.5 |
485 |
do |
625 |
12.2 |
14.5 |
0.214 |
0.1 |
11 |
10 |
| |
| 16 X 1.5 C |
1 |
0.8 |
- |
0.3 |
1.8 |
19.5 |
506 |
do |
646 |
12.2 |
14.5 |
0.214 |
0.1 |
11 |
9 |
| 19 X 1.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
21.0 |
601 |
do |
741 |
12.2 |
14.5 |
0.214 |
0.1 |
10 |
9 |
| 24 X 1.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
24.0 |
738 |
do |
913 |
12.2 |
14.5 |
0.214 |
0.1 |
9 |
8 |
| |
| 27 X 1.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
24.5 |
810 |
do |
985 |
12.2 |
14.5 |
0.214 |
0.1 |
9 |
8 |
| 30 X 1.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
25.5 |
878 |
do |
1158 |
12.2 |
14.5 |
0.214 |
0.1 |
9 |
7 |
| 37 X 1.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
27.0 |
1040 |
do |
1320 |
12.2 |
14.5 |
0.214 |
0.1 |
8 |
7 |
| |
| 2 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
13.0 |
213 |
do |
288 |
7.4 |
8.71 |
0.204 |
0.1 |
32 |
27 |
| 3 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
13.5 |
248 |
do |
323 |
7.4 |
8.71 |
0.204 |
0.1 |
27 |
24 |
| 4 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
14.5 |
289 |
do |
364 |
7.4 |
8.71 |
0.204 |
0.1 |
27 |
24 |
| |
| 5 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
15.5 |
345 |
do |
420 |
7.4 |
8.71 |
0.204 |
0.1 |
23 |
19 |
| 6 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
16.5 |
298 |
do |
538 |
7.4 |
8.71 |
0.204 |
0.1 |
21 |
18 |
| 7 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
16.5 |
420 |
do |
660 |
7.4 |
8.71 |
0.204 |
0.1 |
20 |
17 |
| |
| 10 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
21.0 |
595 |
do |
735 |
7.4 |
8.71 |
0.204 |
0.1 |
18 |
15 |
| 12 X 2.5 C |
1 |
0.9 |
0.3 |
- |
1.8 |
21.5 |
623 |
do |
798 |
7.4 |
8.71 |
0.204 |
0.1 |
17 |
14 |
| 14 X 2.5 C |
1 |
0.9 |
- |
0.3 |
2.0 |
21.5 |
673 |
do |
848 |
7.4 |
8.71 |
0.204 |
0.1 |
16 |
13 |
| |
| 16 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
23.0 |
744 |
do |
919 |
7.4 |
8.71 |
0.204 |
0.1 |
15 |
13 |
| 19 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
24.0 |
857 |
do |
1032 |
7.4 |
8.71 |
0.204 |
0.1 |
14 |
12 |
| 24 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
27.5 |
1068 |
do |
1388 |
7.4 |
8.71 |
0.204 |
0.1 |
13 |
11 |
| |
| 27 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
28.5 |
1170 |
do |
1490 |
7.4 |
8.71 |
0.204 |
0.1 |
12 |
10 |
| 30 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
29.5 |
1279 |
do |
1630 |
7.4 |
8.71 |
0.204 |
0.1 |
12 |
10 |
| 37 X 2.5 C |
1 |
0.8 |
- |
0.3 |
2.0 |
32.0 |
1577 |
do |
1928 |
7.4 |
8.71 |
0.204 |
0.1 |
11 |
9 |
|
| |
| Copper Conductor Control Cables (Armoured) |
TABLE-2 PVC insulated and PVC sheathed armoured multicore 650/1100 V grade copper conductor control cables (1.5 sq. mm & 2.5 sq. mm) |
| Type |
No. of Cores & Cross sectional area |
Con- ductor (Cu) Min. No. of wire |
Thickness of PVC Insulation (Nom) |
Thickness of Common covering (min) |
Armouring |
Thickness of PVC outer sheath (Nom) |
Approx OD |
Approx. net wt. of cable |
Normal Delivery Length in Mtrs. |
Approx gross wt. |
Max. D.C. resistance at 20oC |
Approx AC resis- tance at operating temp. 70oC |
Approx reactance at 50 Hz |
Approx Capaci- tance for two
adja- cent cores |
Current Rating |
| Extruded |
Wrapped |
Flat wire |
Round Wire Dia |
Direct in ground |
In air |
| |
No. x mm2 |
No. |
mm. |
mm. |
mm. |
mm. |
mm. |
mm. |
mm. |
Kg/Km |
|
Kg/km |
ohm/Km |
ohm/km |
ohm/km |
uf/km |
Amps. |
Amps. |
| YWY |
2 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
15.0 |
411 |
500/1000 |
486 |
12.2 |
14.5 |
0.239 |
0.1 |
23 |
20 |
| 3 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
15.5 |
448 |
do |
523 |
12.2 |
14.5 |
0.239 |
0.1 |
21 |
17 |
| 4 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
16.5 |
494 |
do |
634 |
12.2 |
14.5 |
0.239 |
0.1 |
21 |
17 |
| |
| 5 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
17.0 |
560 |
do |
700 |
12.2 |
14.5 |
0.239 |
0.1 |
16 |
14 |
| 6 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
18.0 |
618 |
do |
758 |
12.2 |
14.5 |
0.239 |
0.1 |
15 |
13 |
| 7 X 1.5 C |
1 |
0.8 |
0.3 |
- |
- |
1.40 |
1.8 |
18.0 |
625 |
do |
765 |
12.2 |
14.5 |
0.239 |
0.1 |
14 |
13 |
| |
|
| |
10 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
20.0 |
706 |
500 |
846 |
12.2 |
14.5 |
0.239 |
0.1 |
13 |
11 |
| |
12 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
20.0 |
716 |
do |
856 |
12.2 |
14.5 |
0.239 |
0.1 |
12 |
10 |
| |
14 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
20.5 |
727 |
do |
867 |
12.2 |
14.5 |
0.239 |
0.1 |
11 |
10 |
| |
|
| YFY |
16 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
21.5 |
779 |
do |
954 |
12.2 |
14.5 |
0.239 |
0.1 |
11 |
9 |
| 19 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
22.5 |
874 |
do |
1049 |
12.2 |
14.5 |
0.239 |
0.1 |
10 |
9 |
| 24 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
25.5 |
1060 |
do |
1380 |
12.2 |
14.5 |
0.239 |
0.1 |
9 |
8 |
| |
| 27 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
26.0 |
1148 |
do |
1460 |
12.2 |
14.5 |
0.239 |
0.1 |
9 |
8 |
| 30 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
27.0 |
1235 |
do |
1616 |
12.2 |
14.5 |
0.239 |
0.1 |
9 |
7 |
| 37 X 1.5 C |
1 |
0.8 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
29.0 |
1410 |
do |
1760 |
12.2 |
14.5 |
0.239 |
0.1 |
8 |
7 |
| |
|
| YWY |
2 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
1.8 |
16.0 |
486 |
do |
626 |
7.4 |
8.71 |
0.229 |
0.1 |
32 |
27 |
| 3 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
1.8 |
17.0 |
539 |
do |
679 |
7.4 |
8.71 |
0.229 |
0.1 |
27 |
24 |
| 4 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
1.8 |
17.5 |
608 |
do |
748 |
7.4 |
8.71 |
0.229 |
0.1 |
27 |
24 |
| |
| 5 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
1.8 |
19.0 |
677 |
do |
817 |
7.4 |
8.71 |
0.229 |
0.1 |
23 |
19 |
| 6 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
2.0 |
20.5 |
780 |
do |
920 |
7.4 |
8.71 |
0.229 |
0.1 |
21 |
18 |
| 7 X 2.5 C |
1 |
0.9 |
0.3 |
- |
- |
1.40 |
2.0 |
20.5 |
800 |
do |
940 |
7.4 |
8.71 |
0.229 |
0.1 |
20 |
17 |
| |
|
| |
10 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
22.0 |
800 |
do |
975 |
7.4 |
8.71 |
0.229 |
0.1 |
18 |
15 |
| |
12 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
22.5 |
860 |
do |
1035 |
7.4 |
8.71 |
0.229 |
0.1 |
17 |
14 |
| |
14 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
23.5 |
966 |
do |
1140 |
7.4 |
8.71 |
0.229 |
0.1 |
16 |
13 |
| |
|
| YFY |
16 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
24.5 |
1048 |
do |
1223 |
7.4 |
8.71 |
0.229 |
0.1 |
15 |
13 |
| 19 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
25.5 |
1176 |
do |
1496 |
7.4 |
8.71 |
0.229 |
0.1 |
14 |
12 |
| 24 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
29.5 |
1456 |
do |
1776 |
7.4 |
8.71 |
0.229 |
0.1 |
13 |
11 |
| |
| 27 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.0 |
30.0 |
1554 |
do |
1874 |
7.4 |
8.71 |
0.204 |
0.1 |
12 |
10 |
| 30 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.2 |
32.0 |
1718 |
do |
2064 |
7.4 |
8.71 |
0.204 |
0.1 |
12 |
10 |
| 37 X 2.5 C |
1 |
0.9 |
- |
0.3 |
4.0 X 0.8 |
- |
2.2 |
34.0 |
2004 |
do |
2354 |
7.4 |
8.71 |
0.204 |
0.1 |
11 |
9 |
|
| |
TABLE-1 Unarmoured two core power cables type YY 650/1100 volts grade with copper conductors |
| Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Sq. mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| 1.5 |
0.8 |
0.3 |
1.8 |
10.80 |
150 |
23 |
20 |
500/1000 |
| 2.5 |
0.9 |
0.3 |
1.8 |
11.90 |
190 |
32 |
27 |
500/1000 |
| 4.0 |
1.0 |
0.3 |
1.8 |
13.30 |
250 |
41 |
35 |
500/1000 |
| 6.0 |
1.0 |
0.3 |
1.8 |
14.30 |
320 |
50 |
45 |
500/1000 |
| 10.0 |
1.0 |
0.3 |
1.8 |
16.00 |
430 |
70 |
60 |
500 |
| 16.0 |
1.0 |
0.3 |
1.8 |
16.80 |
550 |
90 |
78 |
500 |
| 25.0 |
1.2 |
0.3 |
2.0 |
19.60 |
800 |
115 |
105 |
500 |
| 35.0 |
1.2 |
0.3 |
2.0 |
21.10 |
1000 |
140 |
125 |
500 |
| 50.0 |
1.4 |
0.3 |
2.0 |
23.70 |
1350 |
165 |
155 |
500 |
| 70.0 |
1.4 |
0.3 |
2.0 |
25.70 |
1760 |
205 |
195 |
500 |
| 95.0 |
1.6 |
0.3 |
2.0 |
29.50 |
2350 |
240 |
230 |
500 |
| 120.0 |
1.6 |
0.4 |
2.2 |
32.00 |
2900 |
275 |
265 |
500 |
| 150.0 |
1.8 |
0.4 |
2.2 |
34.60 |
3500 |
310 |
305 |
250 |
|
| |
TABLE-2 Unarmoured three core power cables type YY 650/1100 volts grade with copper conductors |
| Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Sq. mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| 1.5 |
0.8 |
0.3 |
1.8 |
11.10 |
170 |
21 |
17 |
500/1000 |
| 2.5 |
0.9 |
0.3 |
1.8 |
12.50 |
225 |
27 |
24 |
500/1000 |
| 4.0 |
1.0 |
0.3 |
1.8 |
14.00 |
300 |
36 |
30 |
500/1000 |
| 6.0 |
1.0 |
0.3 |
1.8 |
15.20 |
390 |
45 |
39 |
500/1000 |
| 10.0 |
1.0 |
0.3 |
1.8 |
16.00 |
540 |
60 |
52 |
500 |
| 16.0 |
1.0 |
0.3 |
1.8 |
18.00 |
720 |
77 |
66 |
500 |
| 25.0 |
1.2 |
0.3 |
2.0 |
21.50 |
1070 |
99 |
90 |
500 |
| 35.0 |
1.2 |
0.3 |
2.0 |
23.50 |
1400 |
120 |
110 |
500 |
| 50.0 |
1.4 |
0.3 |
2.0 |
26.90 |
1920 |
145 |
135 |
500 |
| 70.0 |
1.4 |
0.4 |
2.2 |
30.30 |
2550 |
175 |
165 |
500 |
| 95.0 |
1.6 |
0.4 |
2.2 |
34.50 |
3450 |
210 |
200 |
500 |
| 120.0 |
1.6 |
0.4 |
2.2 |
37.50 |
4250 |
240 |
230 |
250/500 |
| 150.0 |
1.8 |
0.5 |
2.4 |
41.50 |
5250 |
270 |
265 |
250 |
|
| |
TABLE-3 Unarmoured three and half core power cables type YY 650/1100 volts grade with copper conductors |
| Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Sq. mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| 25/16 |
1.2/1.0 |
0.3 |
2.0 |
23.50 |
1230 |
99 |
90 |
500 |
| 35/16 |
1.2/1.0 |
0.3 |
2.0 |
25.60 |
1620 |
120 |
110 |
500 |
| 50/25 |
1.4/1.2 |
0.3 |
2.2 |
29.90 |
2300 |
145 |
135 |
500 |
| 70/35 |
1.4/1.2 |
0.4 |
2.2 |
33.10 |
3000 |
175 |
165 |
500 |
| 95/50 |
1.6/1.4 |
0.4 |
2.2 |
37.80 |
4100 |
210 |
200 |
250/500 |
| 120/70 |
1.6/1.4 |
0.5 |
2.4 |
41.40 |
5110 |
240 |
230 |
250/500 |
| 150/70 |
1.8/1.4 |
0.5 |
2.6 |
45.90 |
6170 |
270 |
265 |
250 |
|
| |
TABLE-4 Unarmoured four core power cables type YY 650/1100 volts grade with copper conductors |
| Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Sq. mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| 1.5 |
0.8 |
0.3 |
1.8 |
12.00 |
210 |
21 |
17 |
500/1000 |
| 2.5 |
0.9 |
0.3 |
1.8 |
13.50 |
280 |
27 |
24 |
500/1000 |
| 4.0 |
1.0 |
0.3 |
1.8 |
15.00 |
380 |
36 |
30 |
500/1000 |
| 6.0 |
1.0 |
0.3 |
1.8 |
16.50 |
490 |
45 |
39 |
500/1000 |
| 10.0 |
1.0 |
0.3 |
1.8 |
18.50 |
690 |
60 |
52 |
500 |
| 16.0 |
1.2 |
0.3 |
2.0 |
20.90 |
960 |
77 |
66 |
500 |
| 25.0 |
1.2 |
0.3 |
2.0 |
24.60 |
1420 |
99 |
90 |
500 |
| 35.0 |
1.2 |
0.3 |
2.0 |
27.00 |
1850 |
120 |
110 |
500 |
| 50.0 |
1.4 |
0.4 |
2.2 |
31.60 |
3840 |
145 |
135 |
500 |
| 70.0 |
1.4 |
0.4 |
2.2 |
35.10 |
3600 |
175 |
165 |
500 |
| 95.0 |
1.6 |
0.5 |
2.4 |
40.40 |
4640 |
210 |
200 |
250/500 |
| 120.0 |
1.6 |
0.5 |
2.4 |
43.90 |
5700 |
240 |
230 |
250/500 |
| 150.0 |
1.8 |
0.5 |
2.6 |
48.70 |
7050 |
270 |
265 |
250 |
|
| |
TABLE-5 Armoured two core power cables type YWY and YFY 650/1100 volts grade with copper conductors |
| Type |
Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Armouring |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Round Wire |
Flat wire |
| |
Sq. mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| YWY |
1.5 |
0.8 |
0.3 |
1.4 |
- |
1.8 |
13.30 |
385 |
23 |
20 |
500/1000 |
| 2.5 |
0.9 |
0.3 |
1.4 |
- |
1.8 |
14.50 |
450 |
32 |
27 |
500/1000 |
| 4.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
15.90 |
550 |
41 |
35 |
500/1000 |
| 6.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
16.90 |
640 |
50 |
45 |
500 |
| 10.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
18.50 |
800 |
70 |
60 |
500 |
| YFY |
16.0 |
1.0 |
0.3 |
- |
4x0.8 |
2.0 |
19.10 |
810 |
90 |
78 |
500 |
| 25.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
21.50 |
1100 |
115 |
105 |
500 |
| 35.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
23.00 |
1325 |
140 |
125 |
500 |
| 50.0 |
1.4 |
0.3 |
- |
4x0.8 |
2.0 |
25.50 |
1725 |
165 |
155 |
500 |
| 70.0 |
1.4 |
0.3 |
- |
4x0.8 |
2.0 |
27.50 |
2150 |
205 |
195 |
500 |
| 95.0 |
1.6 |
0.3 |
- |
4x0.8 |
2.0 |
30.90 |
2800 |
240 |
230 |
500 |
| 120.0 |
1.6 |
0.4 |
- |
4x0.8 |
2.2 |
33.20 |
3400 |
275 |
265 |
250/500 |
| 150.0 |
1.8 |
0.4 |
- |
4x0.8 |
2.2 |
36.40 |
4100 |
310 |
305 |
250/500 |
|
| |
TABLE-6 Armoured three core power cables type YWY and YFY 650/1100 volts grade with copper conductors |
| Type |
Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Armouring |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Round Wire |
Flat wire |
| |
Sq. mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| |
1.5 |
0.8 |
0.3 |
1.4 |
- |
1.8 |
13.80 |
420 |
21 |
17 |
500/1000 |
| |
2.5 |
0.9 |
0.3 |
1.4 |
- |
1.8 |
15.10 |
500 |
27 |
24 |
500/1000 |
| |
4.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
16.60 |
625 |
36 |
30 |
500/1000 |
| YWY |
6.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
17.70 |
730 |
45 |
39 |
500 |
| 10.0 |
1.0 |
0.0 |
- |
4x0.8 |
2.0 |
18.60 |
780 |
60 |
52 |
500 |
| 16.0 |
1.0 |
0.3 |
- |
4x0.8 |
2.0 |
20.30 |
1000 |
77 |
66 |
500 |
| 25.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
23.40 |
1400 |
99 |
90 |
500 |
| YFY |
35.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
25.40 |
1750 |
120 |
110 |
500 |
| 50.0 |
1.4 |
0.3 |
- |
4x0.8 |
2.0 |
28.80 |
2325 |
145 |
135 |
500 |
| 70.0 |
1.4 |
0.4 |
- |
4x0.8 |
2.0 |
32.20 |
3050 |
175 |
165 |
500 |
| 95.0 |
1.6 |
0.4 |
- |
4x0.8 |
2.2 |
36.40 |
4000 |
210 |
210 |
500 |
| 120.0 |
1.6 |
0.4 |
- |
4x0.8 |
2.4 |
39.40 |
4860 |
240 |
230 |
250/500 |
| 150.0 |
1.8 |
0.5 |
- |
4x0.8 |
2.4 |
43.30 |
5900 |
270 |
265 |
250/500 |
|
| |
TABLE-7 Armoured three and half core power cables type YWY and YFY 650/1100 volts grade with copper conductors |
| Type |
Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Armouring |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Round Wire |
Flat wire |
| |
Sq. mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| YFY |
25/16 |
1.2/1.0 |
0.3 |
- |
4x0.8 |
2.0 |
25.30 |
1650 |
99 |
90 |
500 |
| 35/16 |
1.2/1.0 |
0.3 |
- |
4x0.8- |
2.0 |
27.60 |
2060 |
120 |
110 |
500 |
| 50/25 |
1.4/1.2 |
0.4 |
- |
4x0.8 |
2.2 |
31.90 |
2800 |
145 |
135 |
500 |
| 70/35 |
1.4/1.2 |
0.4 |
- |
4x0.8 |
2.2 |
35.10 |
3550 |
175 |
165 |
500 |
| 95/50 |
1.6/1.4 |
0.4 |
- |
4x0.8 |
2.4 |
40.20 |
4700 |
210 |
200 |
250/500 |
| 120/70 |
1.6/1.4 |
0.5 |
- |
4x0.8 |
2.4 |
43.40 |
5750 |
240 |
230 |
250/500 |
| 150/70 |
1.8/1.4 |
0.5 |
- |
4x0.8 |
2.6 |
47.70 |
6900 |
270 |
265 |
250 |
|
| |
TABLE-8 Armoured four core power cables type YY 650/1100 volts grade with copper conductors |
| Type |
Cross Sectional Area |
Thickness of PVC Insulation |
Thickness of Inner Sheath |
Armouring |
Thickness of Outer Sheath |
Approx. Outer Diameter |
Approx. Net wt. of the Cable |
Current Direct in Ground |
Rating In Air |
Standard drum Length |
| Round Wire |
Flat wire |
| |
Sq. mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Amps. |
Amps. |
Mtrs. |
| |
1.5 |
0.8 |
0.3 |
1.4 |
- |
1.8 |
14.80 |
470 |
21 |
17 |
500/1000 |
| |
2.5 |
0.9 |
0.3 |
1.4 |
- |
1.8 |
16.30 |
590 |
27 |
24 |
500/1000 |
| |
4.0 |
1.0 |
0.3 |
1.4 |
- |
1.8 |
18.00 |
725 |
36 |
33 |
500/1000 |
| YWY |
6.0 |
1.0 |
0.3 |
1.4 |
- |
2.0 |
19.60 |
890 |
45 |
39 |
500 |
| 10.0 |
1.0 |
0.0 |
- |
4x0.8 |
2.0 |
20.80 |
970 |
60 |
52 |
500 |
| 16.0 |
1.0 |
0.3 |
- |
4x0.8 |
2.0 |
22.80 |
1280 |
77 |
66 |
500 |
| 25.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
26.50 |
1800 |
99 |
90 |
500 |
| YFY |
35.0 |
1.2 |
0.3 |
- |
4x0.8 |
2.0 |
28.90 |
2300 |
120 |
110 |
500 |
| 50.0 |
1.4 |
0.4 |
- |
4x0.8 |
2.2 |
33.50 |
3100 |
145 |
135 |
500 |
| 70.0 |
1.4 |
0.4 |
- |
4x0.8 |
2.2 |
37.00 |
3950 |
175 |
165 |
500 |
| 95.0 |
1.6 |
0.4 |
- |
4x0.8 |
2.4 |
42.30 |
5300 |
210 |
200 |
500 |
| 120.0 |
1.6 |
0.5 |
- |
4x0.8 |
2.6 |
46.30 |
6450 |
240 |
230 |
250/500 |
| 150.0 |
1.8 |
0.5 |
- |
4x0.8 |
2.8 |
50.90 |
7900 |
270 |
265 |
250/500 |
|