Instrumentation Screened Cables & Thermocouple Compensating Cable |
|
| Sl No. |
|
1 Pair X 1.5mm2 Signal Cable |
2 Pair X 1.5mm2 Multicore Signal Cable |
12 Pair X 0.5mm2Multicore Signal Cable |
1 Pair X 1.5mm2 T/C Extn. Cable/
Comp. Cable |
6 Pair X 0.5mm2 T/C Extn. Cable/
Comp. Cable |
12 Pair X 0.5mm2 T/C Extn. Cable/ Comp. Cable |
1 Triad X 1.5mm2 RTD Signal Cable |
6 Triad X 0.5mm2 RTD Signal Cable |
3 Core X 1.5mm2
Power Cable |
| |
|
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Armoured & Screened) |
(Unscreened Armoured ) |
| 1. |
General Application Std. |
|
|
|
|
|
|
|
|
|
| BS5308(Part-2) |
|
|
|
|
|
|
|
|
|
| IS-8130 / 84 |
Yes |
Yes |
Yes |
Yes and |
Yes and |
Yes and |
IS-8130/84 |
IS-8130/84 |
IS-8130/84 |
| IS-5831 / 84 |
|
|
|
ANSI-MC 96.1 |
ANSI-MC 96.1 |
ANSI-MC 96.1 |
|
|
|
| IS-3975 / 88 |
|
|
|
|
|
|
|
|
|
| |
| 2. |
Voltage Grade (RMS) Volts |
660 / 1100 V |
660 / 1100 V |
660 / 1100 V |
660 V |
660 V |
660 V |
660 / 1100V |
660 / 1100V |
1100 V |
| |
| 3. |
Operating Temp. in Deg. C |
90 |
90 |
90 |
90 |
90 |
90 |
90 |
90 |
90 |
| |
Numbers of Cores/Pairs / Triad |
1 Pair |
2 Pair |
12 Pair |
1 Pair |
6 Pair |
12 Pair |
1 - Triad |
6 - Triad |
3 core |
| (A) CONDUCTOR |
| |
Material & Standard |
Annealed Copper |
Annealed Copper |
Annealed Copper |
+VE Chromel/
Copper/ -VE Alumel/Cu-Ni Alloy |
+VE Chromel/ Copper/ -VE Alumel/Cu-Ni Alloy |
+VE Chromell/ Copper/ -VE Alumel/Cu-Ni Alloy |
Annealed Copper |
Annealed Copper |
Annealed Copper |
| |
Conforming To |
IS - 8130/84 |
IS - 8130/84 |
IS - 8130/84 |
ANSI MC. 96.1/ IS : 8784-1987 |
ANSI MC. 96.1/ IS : 8784-1987 |
ANSI MC. 96.1/ IS : 8784-1987 |
IS - 8130/84 |
IS - 8130/84 |
IS - 8130/84 |
| |
| |
Grade |
Electrolytic |
Electrolytic |
Electrolytic |
KX / KX(A) |
KX / KX(A) |
KX / KX(A) |
Electrolytic |
Electrolytic |
Electrolytic |
| |
| |
No. of Strand/Dia of each Strand (mm) |
48/0.2 OR
7/0.53 |
48/0.2 OR
7/0.53 |
16/0.2 OR
7/0.3 |
1/16 AWG
1/20 AWG
3x22 SWG |
1/16 AWG
1/20 AWG
3x22 SWG |
1/16 AWG
1/20 AWG
3x22 SWG |
48/0.2 OR
7/0.53 |
16/0.2 OR
7/0.3 |
48/0.2 OR
7/0.53 |
| |
| |
Pair Identification (by Number markings on Cores at an interval of 250 mm or by number tape on each Core) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Form of Conductor |
Round |
Round |
Round |
Round |
Round |
Round |
Round |
Round |
Round |
| |
| |
Area of Cross Section (sq. mm) |
1.5 |
1.5 |
0.5 |
1.5 |
0.8 OR 1.5 |
0.8 OR 1.5 |
1.5 |
0.5 |
1.5 |
|
| |
| |
Insulation Resitance at 20oC Meg. Ohms/Km (min.) |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
| |
| |
Inductance (Max) Millnry/Km |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
N.A. |
| |
| |
L/R Ratio (Max)
Microhenry/Km |
40 |
40 |
25 |
40 |
25 |
25 |
40 |
25 |
N.A. |
| |
Communication Pair |
NO |
NO |
YES |
NO |
YES |
YES |
NO |
YES |
NO |
| (B) INSULATION |
| |
Insulation PVC Type-A or C 0.6mm nominal thickness to IS-5831/84 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
yes |
| |
| |
Colour Code BS:5308(Part-2) or ANSI or IS:8784 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
yes |
| Tolerance on drum length (+/-5%) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| Bending Radius 12 X 0.0 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
| (C) SCREENING /
SHIELDING (individual + overall)
for multi pair |
| |
Material
|
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
Aluminium
Backed Mylar
Tape |
N.A. |
| |
| |
Percentage Coverage |
100% |
100% |
100% |
100% |
100% |
100% |
100% |
100% |
N.A. |
| |
| |
Overlap % |
25% |
25% |
25% |
25% |
25% |
25% |
25% |
25% |
N.A. |
| |
| |
Thickness (mm) min. 0.05 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
N.A. |
|
| (D) INNER SHEATH |
| |
Material
PVC / HR PVC FRLS |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Type & Standard to which IT conforms
IS-5831/84, ASTM, IEEE |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Extruded (Yes) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Thickness Min. (mm) |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
| |
| |
Colour BS: 5308(Part-2) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Black |
| |
| |
Ripchord shall be provided |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
| (E) ARMOURING |
| |
Material &Type of Armour
(Galvanised Steel Wire / Strip) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Standard to which it conforms IS-3975/88 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Size |
0.9 mm |
0.9 mm |
4x0.8 mm |
0.9 mm |
4x0.8 mm |
4x0.8 mm |
0.9 mm |
4x0.8 mm |
1.4 mm |
| |
| |
Direction (Left Hand) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| (F) OUTER SHEATH |
| |
Material :
PVC / HR PVC / FRLS |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Type & Standard to which it conforms
IS-5831/84, ASTM, IEEE |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| |
| |
Thickness min/nominal (mm) |
1.4 |
1.4 |
1.8 |
1.4 |
1.8 |
1.8 |
1.4 |
1.6 |
1.4 |
| |
| |
Colour Electrical chracteristics (Reqd. for intrinsic safety) |
L. Blue |
L. Blue |
L. Blue |
Brown |
Brown |
Brown |
L. Blue |
L. Blue |
Black |
| (G) ELECTRICAL PARAMETER |
| |
Conductor Resistance (DC) max. at 20 Deg. C Ohm/Km for each Core |
12.2 |
12.2 |
36.6 |
Loop
0.4 / mtr
0.6 / mtr |
Loop
0.4 / mtr
0.6 / mtr |
Loop
0.4 / mtr
0.6 / mtr |
12.2 |
36.6 |
12.2 |
|
| |
| |
Mutual Capacitance
(Max) p F/Km Between
Cores |
250 |
250 |
75 |
250 |
75 |
75 |
250 |
75 |
N.A. |
|
| |
| |
Between Core to
Screen |
400 |
400 |
120 |
400 |
120 |
120 |
400 |
120 |
N.A. |
|
| |
| (H) CHARACTERISTICS OF FRLS SHEATH : |
| (A) |
Oxygen Index |
: |
Minimum 29% at Room Temperature when tested as per ASTM-D-2863 |
| (B) |
Temperature Index |
: |
Minimum 250 Deg. C at Oxygen Index when tested as per ASTM-D-2863 |
| (C) |
Acid Gas Generation |
: |
Minimum 20% by weight when tested as per IEC-754 Part-1 |
| (D) |
Smoke Density Rating |
: |
Minimum 60% when tested as per ASTM-D-2843 |
| (E) |
Flammability Test |
|
As per IEC 332 Part 1 & 2 / 1979 |
|
| N.B. WE ALSO MANUFACTURE AS PER CUSTOMISED TAILOR-MADE SPECIFICATIONS |
|